Connections, displays and control elements: | ||
Digital outputs: | 12 x digital outputs 6V - 30V, 500mA | |
Grouping of 2 outputs Grouping of 4 outputs | ||
Maximum group current 2 A | ||
Maximum total current 6 A | ||
Short-circuit-protected | ||
Using our coupling relays voltages of even up to 230V can be switched | ||
Digital inputs: | 12 x digital inputs, | |
Max. input voltage +/-30 V | ||
Protected against polarity reversal within this range | ||
Switching threshold 8V +/- 1V | ||
"On" current = 2.2 mA | ||
integrated 32-bit counter | ||
Network: | 10 / 100BaseT autosensing | |
Power supply: | 12-24V DC (approx. 100mA@24V) | |
Galvanic isolation: | Digital outputs - network: min. 1000 V | |
Digital inputs - network: min. 2000 V | ||
Digital inputs - outputs: min. 1000 V | ||
Connections: | 2 x 16x screw terminal blocks for IOs and power 1 x RJ45 for network 1 x DB9 plug for RS232 | |
Displays: | Status LEDs for network | |
12 LEDs for digital status | ||
Data transmission: | ||
Protocols: | TCP and UDP sockets, client and server | |
SNMP including traps | ||
SMTP e-mail sending | ||
OPC server | ||
Modbus TCP | ||
Inventory keeping, group management | ||
Response times: | Data and switching traffic: typically 12 ms | |
Housing and other data: | ||
Housing: | Plastic housing for top hat rail installation | |
106.8 x 87.8 x 62.6 (L x W x H) | ||
Enclosure rating: | IP20 | |
Weight: | approx. 250 g | |
Storage temperature: | -25°C - 70°C | |
Operating temperature: | 0°C - 60°C | |
Permissible relative humidity: | 5..95% RH (non-condensing) | |
MTBF: | 245,100 h @25°C per MIL-HDBK-217 | |
Scope of delivery: | 1 x Web-IO 12xDigital, |